EasyManua.ls Logo

Delta Modulon DPH series - Page 155

Delta Modulon DPH series
232 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6-37
6
UPS Operation
3
After selection of YES’, the UPS will shut down the inverter, terminate each power
module’s output and transfer to run in standby mode. At this moment, the tri-color LED
indicator illuminates yellow and the following screen appears (Figure 6-50). For the tri-
color LED indicator location, please refer to Figure 2-11.
Standby
POWER FLOW
Maintenance
Bypass
Bypass
Mains
90 %
5 mins
Load
0 %
MEASUREMENT
Power Flow
UPS-1.1 SETUP
MAINTENANCE
Power Flow
Summary
System Status
LOG IN
User
2
WARNING
10:15
May 25,2018
(Figure 6-50: Standby Mode Screen)
4
Single Input:
Switch OFF the UPS’s bypass switch (Q0), Delta or non-Delta external maintenance
bypass cabinet’s input breaker or switch (Q1) and output breaker or switch (Q4).
Dual Input:
Switch OFF the UPS’s bypass switch (Q0), Delta or non-Delta external maintenance
bypass cabinet’s input breaker or switch (Q1), bypass breaker or switch (Q2) and output
breaker or switch (Q4).
5
Now, each power module performs DC BUS discharging and its LED indicator flashes
green. After discharging, each power module’s LED indicator will be off.
6
About 3 minutes later, the UPS will shut down. After that, the LCD and the tricolor LED
indicator will be off.
7
Switch OFF every external battery cabinet’s breaker (Q5).

Table of Contents

Related product manuals