2.5 Temperature Measurement Modules Specifications
2.5.1 General Specifications
AS04RTD-A / AS06RTD-A
Electrical specifications
Number of analog
inputs
AS04RTD-A: four ; AS06RTD-A: six
Applicable sensor
2-WIRE & 3-WIRE
Pt100: DIN 43760-1980 JIS C1604-1989; 100 Ω 3850 PPM/°C
Pt1000: DIN EN60751; 1 k Ω 3850 PPM/°C
Ni100/Ni1000: DIN 43760
JPt100: JIS C1604-1989LG-Ni1000
Cu50/Cu100
Ni120 (available for FW V1.06 or later)
0–300 Ω/03000 Ω
Supply voltage
24 VDC (20.4 VDC28.8 VDC) (-15% to +20%)
Connector type
Removable terminal block
Overall accuracy
Pt100/Ni100/Ni120/Pt1000/Ni1000/JPt100:
25°C/77°F: The error is ±0.1% of the input within the range.
-20 to +60°C/-4 to +140°F: The error is
±
0.5% of the input within the range.
LG-Ni1000: 25°C/77°F: The error is ±0.2% of the input within the range.
Cu50: 25°C/77°F: The error is
±
4°C of the input within the range.
Cu100: 25°C/77°F: The error is ±2°C of the input within the range.
Resolution
0.1°C / 0.1°F
Conversion time
Two-wire/three-wire configuration: 200 ms/channel
Isolation
An analog circuit is isolated from a di
gital circuit by a digital integrated circuit/an
optocoupler, and the analog channels are isolated from one another by
optocouplers.
Isolation between a digital circuit and a ground: 500 VAC
Isolation between an analog circuit and a ground: 500 VAC
Isolation between an analog circuit and a digital circuit: 500 VAC
Isolation between the 24 VDC and a ground: 500 VAC
Weight
AS04RTD-A: 115g ; AS06RTD-A: 125g