(4) Keep the input cables, output cables, and power cable separate from one another.
(5) If the main circuit and the power cable cannot be separated from each other, use a shielded cable,
and ground it at the side of the I/O module. In some cases, the shielded cable can be grounded at the
opposite side.
(6) If you wire a module through conduit, you must ground the conduit correctly.
(7) Keep 24 VDC input cables separate from 110 VAC input cables and 220 VDC input cables.
(8) If the wiring length is more than 200 meters (656.19 feet), leakage current can result from parasitic
capacitance, and the system will not function properly.
Shielded cable
AC pow
er
supply
Load through which the
alternating current passes