EasyManua.ls Logo

Delta M60U

Delta M60U
130 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Figure 3-22: Two optional Locations for AC terminal (121 Model Without RSD)
After inserting conductor,
torque terminal screw to 49.5 lbf-in (5.6 Nm)
EMT
Bottom entry option using
2" (max) trade size raceway
After inserting conductor,
torque terminal screw to
31 lbf-in (3.5 Nm)
Refer to Figure 3-17 in Section 3.3 for the procedure to prepare AC conductors
for connection to the AC terminals (M80/60U
_121) :
Ensure the AC conductors used are sized to the correct ampacity per NEC or
other local code. Refer to Figure 3-17.
- Open all AC switch cage-clamps as noted in Section 3.3.4
- Ensure the correct conductor is connected to the appropriate terminal.
- After conductor is inserted, tighten L1~N terminal with a torque value of
31 lbf-in (3.5 Nm), PE terminal with 49.5 lbf-in (5.6 Nm).
- Insert the EGC (1~2/0 AWG) into the grounding screw terminal, torque value
of 80 lbf-in (9 Nm). (see Figure 3-22)
3.3.7
AC Wiring for M80/60U_121 models (Without RSD)
L3L2L1
NN PE
PE
AC switch
After inserting conductor,
torque terminal screw to 80 lbf-in (9 Nm)
Allowable PE conductor size 1~2/0 AWG (35~50mm²)
Grounding screw terminal
PEPE
45
Installation

Table of Contents

Related product manuals