Wiring Instructions
Installation Manual
40
1/0 Power Cable
Metal Conductor
Two-hole Lug
Preparing AC/DC Cables
The following guidelines describe how to prepare the AC/DC cables for a grid connection.
When crimping cable, a hexagonal crimping method is recommended.
1.
Strip the head of the insulator of the AC and DC power cables. Insert the exposed part of the
power cable into the junction hole of the corresponding cable lug, which is available from the
accessary kit.
2.
Continue inserting the cable until its head reaches the wire inspection indicator, as shown in the
following figure:
Figure 43. Inserting a Power Cable into a Cable Lug, Depth Reference Diagram
3.
For safety purpose, use heat shrinkable tubing on the junction between the cables and lugs. The
voltage rating of the heat shrinkable tubing should be at least 1000 V for DC power cable or 600
V for AC power cable. Make sure the exposed part of the junction between the cables and lugs
is fully covered by the tubing, as shown in the following figures.
4.
Prepare the cables as follows:
Type A
Type B
Figure 44. Preparation of AC/DC Cables
Wire Inspection Indicator
Heat Shrinkable Tubing