Appendix
Installation Manual
60
Appendix
Specifications
Table 17: Technical Specifications of the Delta PCS100
Item
Description
Grid-tied Operation
Rated Grid Voltage
400 Vac, 3 phase
Grid Voltage Range
312 to 459 Vac
Rated Grid Frequency
50 Hz (60 Hz optional)
Frequency Range
45 to 55 Hz, adjustable
Rated AC Power
100 kVA
Rated AC Current
144.3 A
Max. Continuous AC Current
160.4 Arms
Current THD
< 3% at rated power
Power Factor
-1 to 1, continuously adjustable
Charging-discharging transfer time
< 100 ms
Power response time
< 40 ms
Battery Input Performance
DC Voltage Range
600 to 1,000 Vdc
Rated DC Voltage
900 Vdc
Rated Discharge Power
103 kW
Rated Charge Power
97 kW
Max. Discharge DC Current
171.7A
Max. Charge DC Current
161.7A
Standalone Mode Performance
Rated Output Voltage
400V, 3P3W
(3P4W, extra transformer needed )
Rated Output Power
100kVA/ 100kW with linear load
100kVA with RCD load (CF 2)
Rated Output Current
144.3 A
Rated Output Frequency
50 Hz ± 1%
Power Factor
0.8 to 1
Output Voltage Accuracy
1%
Voltage Symmetry
± 1%, @ 100% linear balanced load
Output Voltage THD
< 3% @ 12.5 ~ 100% liner load
< 5% @ 12.5 ~ 100% RCD load (Crest factor ≤ 2.0)
Output Voltage Regulation
< 10%, at dynamic; Recovering within tolerance in 100 ms