Table 17: Technical Specifications of Delta PCS100 (Continued)
Table 18: Icc declaration (r.m.s. value, Icp,mr, device)
≤ 2000 m: -25 ~ 60ºC, derating > 50ºC (3%/ºC),
-25 ~ 40ºC, > 2000 m
0 to 95% RH, no-condensing
Fan cooled, speed controlled and alarmed signal
Interface & Communication
3 x Input, 0 - 24 V
2 x Output relays
4.9 inch LCD screen with operation button, Fault LEDs
Local EPO button & remote control
RS-485 / Modbus RTU, Ethernet/ Modbus TCP
Dimensions (W x D x H) (excl.
Package)
600 mm x 800 mm x 1,766 mm / 23.6 in x 31.5 in x 69.5 in
Net Weight (excl. Package)
IEC/EN 62477-1,
VDE-AR-N4105, G99, AS/NZS 4777.2
IEC/EN 61000-6-2, IEC/EN 61000-6-4 (Class A)
Applicable Battery Chemistry
Lithium-ion, flow battery
Rated current: 250A; rated voltage:690V;
Interrupt rating: 200kA RMS Sym.
Rated current: 250A; rated voltage:1000V;
breaking capacity: 50kA.