Table 4: Grounding Wire Sizing and Ratings (Continued)
Communication and I/O Wire Sizing and Ratings
Here are the requirements for the communication and I/O wires:
Table 5: Communication and I/O Wire Sizing and Ratings
The following connectors, enclosed in accessory kit:
8 for CNJ3, 15-pin connector
2 for CNJ5, 2-pin connector
5 for CNJ13, 6-pin connector
8x2 for CNJ11, CNJ12, 8-pin RJ45 connector
Preparation of Cables
This section describes how to prepare the cable prepare the corresponding cables and wires to meet
the specified requirements, see “Wire Sizing and Ratings” on page 37.
The following items require preparation:
2 x 1000V, 53.49 mm
2
(1/0 AWG) cables for DC (battery) connection
6 x 600V or greater, 33.62 ~ 53.49 mm2 (2 AWG ~ 1/0 AWG) cables for AC connection
1 x 600V or greater, 26.67~ 53.49 mm2 cables for grounding
29 x 600V or greater, 16 AWG wires for communication or I/O connection
9 x 2-hole cable lugs
1 x 15-pin green connector (enclosed in the accessory kit)
2 x 6-pin green connector (enclosed in the accessory kit)
1 x 2-pin green connector (enclosed in the accessory kit)
1 x 3-pin green connector (enclosed in the accessory kit)
2 x RJ45 connector
Note:
Wiring must comply with the IEC standard and local regulations.