EasyManua.ls Logo

Delta RPI M50A

Delta RPI M50A
228 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.2 Preparation Before Wiring (Models without Fuse)
RPI M30A_121 does not have internal strings fuse. Each string can accept
maximum current 30A. It can use one pair of DC connector for each input
(DC1 and DC2)
For floating PV array, inverter can accept DC input in parallel connection
or separate connection.
• When grounding the solar array, an isolation transformer at AC side is
required and DC inputs must be parallel connection due to the RPI-series
not having galvanic isolation between the DC-input and AC-output.
When solar array is grounded,the PID function can not be enable,and the
insulation have to be setting “Plus Grounded” or “Minus Grounded”.
Different DC connection type needs different settings of insulation detection.
About setting, please refer to 5.2.7 Install Settings.
Figure 4-5 floating string of M30A_121
1
2
3
4
L1
L2
L3
N
PE
Communication
Wiring
1
2
3
PV Array
AC Wiring
DC Wiring
Parallel or
Separate
*
* RPI M30A can support 3P3W system.
DC Distribution box
DC1 DC2
21
Wiring

Table of Contents

Other manuals for Delta RPI M50A

Related product manuals