Figure 5-11 Insulation page
Figure 5-12 Country page
5.2.7.2. Insulation
Before connecting to grid, inverter will measure the impedance between
the PV array and PE first. M30A & M50A models provide 4 types of
impedance measurement methods (ON, Plus Grounded, Minus Grounded,
and OFF) and 2 impedance limits. Installer must select the appropriate
method based on PV array’s wiring.
5.2.7.3. Country
Each country has its own electricity regulations. Installer must select the
country correctly.
ENT
EXIT
ENT
EXIT
EXIT
Inverter ID: 002
Insulation
Country
Grid Settings
Mode: ON
Resistance: 1200k
ON
Plus Grounded
Minus Grounded
OFF
ENT
EXIT
Mode: ON
Resistance: 1200k
1200k
700k
ENT
EXIT
Inverter ID: 002
Insulation
Country
Grid Settings
AU/NZ
Austria
Belgium
China
46