Chapter 5 Parameters_VFD-B Series
5-82
Revision 10/2005, BE13, SW V4.08

When Pr.07-12 and Pr.07-13 are set to 10.00 sec, its response time for the compensation will be the
longest. But if the settings are too short, unstable system may occur.
07 - 14
Accumulative Motor Operation Time (Min.) Unit: 1
Settings 00 ~1439 Factory Setting: 00
07 - 15
Accumulative Motor Operation Time (Day) Unit: 1
Settings 00 ~65535 Factory Setting: 00

Pr.07-14 and Pr.07-15 are used to record the motor operation time. They can be cleared by setting to 00
and time is less than 60 seconds is not recorded.

Table of Contents

Other manuals for Delta VFD-B Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD-B Series and is the answer not in the manual?

Delta VFD-B Series Specifications

General IconGeneral
SeriesVFD-B
Cooling MethodFan cooling
Overload Capacity150% for 60 seconds
Braking UnitBuilt-in
Control ModeV/F control, Sensorless Vector Control
CommunicationRS-485
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Overload, Overtemperature, Short Circuit
Operating Temperature-10°C to +50°C
Storage Temperature-20°C to +60°C
Humidity90% RH (non-condensing)
Altitude1000m (Derating required above 1000m)