Chapter 2 Installation and Wiring_VFD-B Series
Revision 10/2005, BE13, SW V4.08 2-21

If the AC motor drive has a built-in brake chopper (all models of 11kW and below), connect the
external brake resistor to the terminals [
Ѐ
2/B1, B2].

Models of 15kW and above don’t have a built-in brake chopper. Please connect an external optional
brake unit (VFDB-series) and brake resistor. Refer to VFDB series user manual for details.

Connect the terminals [+(P), -(N)] of the brake unit to the AC motor drive terminals [+2(+2/B1), (-)].
The length of wiring should be less than 5m with twisted cable.

When not used, please leave the terminals [+2/B1, -] open.
WARNING!

Short-circuiting [B2] or [-] to [+2/B1] can damage the AC motor drive.
Grounding terminals (
)

Make sure that the leads are connected correctly and the AC drive is properly grounded. (Ground
resistance should not exceed 0.1
Ө
.)

Use ground leads that comply with local regulations and keep them as short as possible.

Multiple VFD-B units can be installed in one location. All the units should be grounded directly to a
common ground terminal, as shown in the figure below. Ensure there are no ground loops.
goodexcellent
not allowed
2.4.4 Control Terminals
Circuit diagram for digital inputs (SINK current 16mA.)
+24
SINK Mode
multi-input
terminal
Internal CircuitDCM
+24V
Multi-Input
Terminal
DCM
Internal Circuit
SOURCE Mode

Table of Contents

Other manuals for Delta VFD-B Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD-B Series and is the answer not in the manual?

Delta VFD-B Series Specifications

General IconGeneral
SeriesVFD-B
Cooling MethodFan cooling
Overload Capacity150% for 60 seconds
Braking UnitBuilt-in
Control ModeV/F control, Sensorless Vector Control
CommunicationRS-485
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Overload, Overtemperature, Short Circuit
Operating Temperature-10°C to +50°C
Storage Temperature-20°C to +60°C
Humidity90% RH (non-condensing)
Altitude1000m (Derating required above 1000m)