Chapter 5 Parameters_VFD-B Series
5-96
Revision 10/2005, BE13, SW V4.08
RTU mode:
Command message:
Response message:
Address 01H
Address 01H
Function 03H
Function 03H
21H
Starting data address
02H
Number of data
(count by byte)
04H
00H 17H Number of data
(count by word)
02H
Content of address
2102H
70H
CRC CHK Low 6FH 00H
CRC CHK High F7H
Content of address
2103H
00H
CRC CHK Low FEH
CRC CHK High 5CH
(2) 06H: single write, write single data to register.
Example: writing data 6000(1770H) to register 0100H. AMD address is 01H.
ASCII mode:
Command message: Response message:
STX ‘:’ STX ‘:’
‘0’ ‘0’
Address
‘1’
Address
‘1’
‘0’ ‘0’
Function
‘6’
Function
‘6’
‘0’ ‘0’
‘1’ ‘1’
‘0’ ‘0’
Data address
‘0’
Data address
‘0’
‘1’ ‘1’
‘7’ ‘7’
‘7’ ‘7’
Data content
‘0’
Data content
‘0’
‘7’ ‘7’
LRC Check
‘1’
LRC Check
‘1’
CR CR
END
LF
END
LF

Table of Contents

Other manuals for Delta VFD-B Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD-B Series and is the answer not in the manual?

Delta VFD-B Series Specifications

General IconGeneral
SeriesVFD-B
Cooling MethodFan cooling
Overload Capacity150% for 60 seconds
Braking UnitBuilt-in
Control ModeV/F control, Sensorless Vector Control
CommunicationRS-485
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Overload, Overtemperature, Short Circuit
Operating Temperature-10°C to +50°C
Storage Temperature-20°C to +60°C
Humidity90% RH (non-condensing)
Altitude1000m (Derating required above 1000m)