Chapter 5 Parameters_VFD-B Series
Revision 10/2005, BE13, SW V4.08 5-115

When output frequency
d
sleep frequency and time > detection time, it will go in sleep mode.

When min. output frequency
Љ
PID frequency
Љ
lower bound of frequency and sleep function is enabled
(output frequency
d
sleep frequency and time > detection time), frequency will be 0 (in sleep mode). If
sleep function is disabled, frequency command = lower bound frequency.

When PID frequency < min. output frequency and sleep function is enabled (output frequency
d
sleep
frequency and time > detection time), output frequency =0 (in sleep mode).
If output frequency
d
sleep frequency but time < detection time, frequency command = lower frequency. If
sleep function is disabled, output frequency =0.

Table of Contents

Other manuals for Delta VFD-B Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD-B Series and is the answer not in the manual?

Delta VFD-B Series Specifications

General IconGeneral
SeriesVFD-B
Cooling MethodFan cooling
Overload Capacity150% for 60 seconds
Braking UnitBuilt-in
Control ModeV/F control, Sensorless Vector Control
CommunicationRS-485
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Overload, Overtemperature, Short Circuit
Operating Temperature-10°C to +50°C
Storage Temperature-20°C to +60°C
Humidity90% RH (non-condensing)
Altitude1000m (Derating required above 1000m)