EasyManua.ls Logo

Delta VFD-ED Series

Delta VFD-ED Series
447 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12 Descriptions of Parameter Settings | VFD-ED
12-01-8
There are two methods for sending leveling signals:
1. Using multi-function input terminals (MI=53)
2. Deactivate MI1 and MI2 (Multi-step speed command 1 and 2)
Method 1: Direct docking terminal function (using MI terminal to input leveling signals)
The steps to execute direct docking terminal function using multi-function input terminal (MI=53) are as
follows:
1. The control mode should be in closed-loop. Set Pr.00-01 = 2 (FOCPG) or 3 (FOCPM).
2. Set Pr.00-14 = 3 (External digital input).
3. Set Pr.00-15 = 1 (External terminals).
4. Set Pr.04-00 = 0 (Zero-step speed frequency must be set to 0 Hz).
5. Increase Pr.01-13 appropriately in case the elevator stops while having not reached the leveling plate.
6. Set Pr.01-35 (Limit for Direct Docking Terminal Function). In normal condition, there is no need to
adjust this parameter.
7. Set Pr.01-36 (Deceleration Distance for Direct Docking Terminal Function). Enter the length of leveling
plate.
8. Set Pr.01-38 = 2 (Direct docking terminal function enabled).
9. Set multi-function input (MI) terminal to 53.
10. Set Pr.11-01 (Elevator speed). Deceleration speed for terminal function direct docking is calculated
according to this parameter
NOTE: Before the terminal function direct docking is activated, all speed commands must be disabled
(zero-step speed = 0 Hz).
RUN command
Elevator runs in high speed
During deceleration, when
the host controller receives
signals of LU, LD or docking,
it sends an MI (=53) signal
to VFD-ED.
Disable all speed comm ands
(zero-step speed = 0 Hz)
Elevator starts
Elevator stops
Executes direct docking
according to Pr.01-
36
deceleration distance

Table of Contents

Related product manuals