12 Descriptions of Parameter Settings | VFD-ED
12-01-10
Automatic Emergency Deceleration Level
Control Mode
VFPG FOCPG
FOCPM
Default: 60.00
Settings 5.00299.00 Hz
When MI is set to 56, the system monitors the current speed. If the speed is higher than Pr.01-39, the
drive decelerates to Pr.01-29 speed according to Pr.01-40 deceleration time.
Deceleration Time for Emergency Deceleration
Control Mode
VFPG FOCPG
FOCPM Default: 2.00
Settings 0.00600.00 sec.
When MI=55 function is triggered, the drive decelerates to Pr.01-29 speed according to Pr.01-40
deceleration time, as shown in the figure below.