12 Descriptions of Parameter Settings | VFD-ED
12-05-5
Slip Compensation Gain % (electricity mode)
Control Mode
VF SVC Default: 0.0
Settings 0.0100.0%
When in VF mode, you do NOT have to set Pr.05-13. To satisfy the demand for different compensation
gains in power generation mode and electricity mode, set Pr.05-23 and Pr.05-24.
When in SVC mode, set Pr.05-13 first. To satisfy the demand for different compensation gains in power
generation mode and electricity mode, set Pr.05-23 and Pr.05-24.