Chapter 12 Description of Parameter SettingsMS300 (High Speed Model)
12-06-23
1
st
fault 2
nd
fault 3
rd
fault 4
th
fault 5
th
fault 6
th
fault
06-63 1000 560 120 1120 680 240
06-64 0 1 2 2 3 4
06-65 0 1000 560 120 1120 680
06-66 0 0 1 2 2 3
06-67 0 0 1000 560 120 1120
06-68 0 0 0 1 2 2
06-69 0 0 0 1000 560 120
06-70 0 0 0 0 1 2
By time record, it can be known that the last fault (Pr. 06-17) happened after the drive run for 4
days and 240 minutes.
Low Current Setting Level
Factory Setting: 0.0
Settings 0.0 ~ 100.0 %
Low Current Detection Time
Factory Setting: 0.00
Settings 0.00 ~ 360.00 sec.
Treatment for Low Current
Factory Setting: 0
Settings
0 : No function
1 : Warn and coast to stop
2 : Warn and ramp to stop by 2
nd
deceleration time
3 : Warn and operation continue
The drive will operate as the setting of Pr. 06-73 when output current is lower than the setting of
Pr. 06-71 and when low current exceeds detected time Pr. 06-72. This parameter can be used
with external multi-function output terminal 44 (for low current output).
The low current detection function will not be executed when drive is at sleep or standby status.