Chapter 12 Description of Parameter SettingsMS300 (High Speed Model)
12-07-4
Time
B.B. Speed tracking: from minimum output frequency
Input B.B. signal
Stop output voltage
Disable B.B. signal
Waiting time Pr. 07-08
Speed tracking
Synchronous speed detection
Output frequency (H)
Output voltage (V)
Output current
Pr. 07-09
Current level of
speed tracking
FWD Run
B.B.
A
B.B.
A
Time
Over-current stall prevention
Output frequency (H)
Output voltage (V)
Output current
Pr. 06-03
Over-current stall
prevention level
during accel.
FWD Run
Input B.B. signal
Stop output voltage
Disable B.B. signal
Waiting time Pr. 07-08
Speed tracking
Synchronous speed detection
Current Limit of Speed Tracking
Factory Setting: 100
Settings 20~200 %
The AC motor drive will execute the speed tracking only if the output current is greater than the
value set by Pr. 07-09.
The maximum current of speed tracking will affect the synchronous time. The larger the
parameter setting is, the faster the synchronization arrives. However, if parameter setting is too
large, overload protection function may be activated.