Chapter 12 Description of Parameter SettingsMS300 (High Speed Model)
12-14-1
14 Protection Parameters (2) This parameter can be set during operation.
Output Frequency at Malfunction 2
Output Frequency at Malfunction 3
Output Frequency at Malfunction 4
Output Frequency at Malfunction 5
Output Frequency at Malfunction 6
Factory Setting: Read only
Settings 0.0~1500.0 Hz
When error occurs, user can check output frequency at malfunction. If the error happens again,
this parameter will cover previous record.
DC Voltage at Malfunction 2
DC Voltage at Malfunction 3
DC Voltage at Malfunction 4
DC Voltage at Malfunction 5
DC Voltage at Malfunction 6
Factory Setting: Read only
Settings 0.0~6553.5 V
When error occurs, user can check DC voltage at malfunction. If the error happens again, this
parameter will cover previous record.
Output Current at Malfunction 2
Output Current at Malfunction 3
Output Current at Malfunction 4
Output Current at Malfunction 5
Output Current at Malfunction 6
Factory Setting: Read only
Settings 0.00~655.35 Amp
When error occurs, user can check output current at malfunction. If the error happens again,
this parameter will cover previous record.
IGBT Temperature at Malfunction 2
IGBT Temperature at Malfunction 3
IGBT Temperature at Malfunction 4
IGBT Temperature at Malfunction 5
IGBT Temperature at Malfunction 6
Factory Setting: Read only
Settings -3276.7~3276.7
o
C
When error occurs, user can check IGBT temperature at malfunction. If the error happens again,
this parameter will cover previous record.