Pr. Explanation Settings Default
00-22 Stop method
0: Ramp to stop
1: Coast to stop
2: Motor stops by simple positioning
0
00-23 Control of motor direction
0: Enable forward and reverse
1: Disable reverse
2: Disable forward
0
00-24
Digital keypad frequency
command memory
Read only Read only
00-25
User-defined
characteristics
bit 0–3: user-defined decimal places
0000b: no decimal place
0001b: one decimal place
0010b: two decimal places
0011b: three decimal places
0
bit 4–15: user-defined unit
000xh: Hz
001xh: rpm
002xh: %
003xh: kg
004xh: m/s
005xh: kW
006xh: HP
007xh: ppm
008xh: l/m
009xh: kg/s
00Axh: kg/m
00Bxh: kg/h
00Cxh: lb/s
00Dxh: lb/m
00Exh: lb/h
00Fxh: ft/s
010xh: ft/m
011xh: M
012xh: ft
013xh: degC
014xh: degF
015xh: mbar
016xh: bar
017xh: Pa
018xh: kPa
019xh: mWG