Chapter 12 Description of Parameter SettingsME300
12.1-03-17
Multi-function MO Output by AI Level Source
Default: 0
Settings 0: AVI
1: ACI
AI Upper Level 1
Default: 50
Settings -100–100%
AI Lower Level 2
Default: 10
Settings -100–100%
Multi-function output terminal 67 must work with Pr.03-44 to select input channels. When analog
input level is higher than Pr.03-45, multi-function output acts; when analog input level is lower
than Pr.03-46, multi-function output terminals stop outputting.
When setting levels, AI upper level must be higher than AI lower level.
Analog Input Curve Selection
Default: 0
Settings 0: Regular Curve
1: Three-point curve of AVI (& AI10)
2: Three-point curve of ACI (& AI11)
ACI Lowest Point
Default: 4.00
Settings Pr.03-28 ≠ 1, 0.00–20.00 mA
ACI Proportional Lowest Point
Default: 0.00
Settings Pr.03-28 ≠ 1, 0.00–100.00%
ACI Mid-point
Default: 12.00
Settings Pr.03-28 ≠ 1, 0.00–20.00 mA
ACI Proportional Mid-point
Default: 50.00
Settings Pr.03-28 ≠ 1, 0.00–100.00%
ACI Highest Point
Default: 20.00
Settings Pr.03-28 ≠ 1, 0.00–20.00 mA
ACI Proportional Highest Point
Default: 100.00
Settings Pr.03-28 ≠ 1, 0.00–100.00%