Chapter 11 Summary of Parameter SettingsC2000 Plus
11-44
09 Communication Parameters
Pr. Parameter Name Setting Range Default
09-00
Modbus Slave Communication
Address
1–254
1
09-01 COM1 Modbus Transmission Speed 4.8–115.2 Kbps 9.6
09-02
COM1 Modbus Transmission Fault
Treatment
0: Warn and continue operation
1: Fault and ramp to stop
2: Fault and coast to stop
3: No warning, no fault and continue operation
3
09-03 COM1 Modbus Time-Out Detection 0.0–100.0 sec. 0.0
09-04
COM1 Modbus Communication
Protocol
1 : 7, N, 2 (ASCII)
2 : 7, E, 1 (ASCII)
3 : 7, O, 1 (ASCII)
4 : 7, E, 2 (ASCII)
5 : 7, O, 2 (ASCII)
6 : 8, N, 1 (ASCII)
7 : 8, N, 2 (ASCII)
8 : 8, E, 1 (ASCII)
9 : 8, O, 1 (ASCII)
10 : 8, E, 2 (ASCII)
11 : 8, O, 2 (ASCII)
12: 8, N, 1 (RTU)
13: 8, N, 2 (RTU)
14: 8, E, 1 (RTU)
15: 8, O, 1 (RTU)
16: 8, E, 2 (RTU)
17: 8, O, 2 (RTU)
1
09-09
Modbus Communication Response
Delay Time
0.0–200.0 ms 2.0
09-10 Communication Main Frequency 0.00–599.00 Hz 60.00
09-11 Block Transfer 1 0000–FFFFh 0000h
09-12 Block Transfer 2 0000–FFFFh 0000h
09-13 Block Transfer 3 0000–FFFFh 0000h
09-14 Block Transfer 4 0000–FFFFh 0000h
09-15 Block Transfer 5 0000–FFFFh 0000h
09-16 Block Transfer 6 0000–FFFFh 0000h
09-17 Block Transfer 7 0000–FFFFh 0000h
09-18 Block Transfer 8 0000–FFFFh 0000h
09-19 Block Transfer 9 0000–FFFFh 0000h
09-20 Block Transfer 10 0000–FFFFh 0000h