Chapter 11 Summary of Parameter SettingsMS300 (High Speed Model) 
 
11-5
 
Pr.  Explanation  Settings 
Factory 
Setting
 
00-26  Max. user defined value 
0: Disable 
0~65535 (when Pr. 00-25 set to no decimal place) 
0.0~6553.5 (when Pr. 00-25 set to 1 decimal place) 
0.00~655.35 (when Pr. 00-25 set to 2 decimal place) 
0.000~65.535 (when Pr. 00-25 set to 3 decimal place) 
0 
 
00-27  User defined value  Read only 
Read 
only 
 
00-29  LOCAL / REMOTE selection 
0: Standard HOA function 
1: Switching Local / Remote, the drive stops 
2: Switching Local / Remote, the drive runs as the 
REMOTE setting for frequency and operation status 
3: Switching Local / Remote, the drive runs as the LOCAL 
setting for frequency and operation status   
4: Switching Local / Remote, the drive runs as LOCAL 
setting when switch to Local and runs as REMOTE 
setting when switch to Remote for frequency and 
operation status. 
0 
 
00-30 
Source of the master 
frequency command (HAND) 
0: Digital keypad   
1: Communication RS-485 input 
2: External analog input (Refer to Pr. 03-00) 
3: External UP / DOWN terminal 
6: CANopen communication card   
7: Digital keypad dial 
8: Communication card (not includes CANopen card) 
[Note]:  
Need to use with MO setting as 41, or use with KPC-CC01
0 
 
00-31 
Source of the operation 
command (HAND) 
0: Digital keypad 
1: External terminals 
2: Communication RS-485 input   
3: CANopen communication card 
5: Communication card (not includes CANopen card)   
[Note]:  
Need to use with MO setting as 41, or use with KPC-CC01
0 
 
00-32  Digital keypad STOP function 
0: STOP key disable 
1: STOP key enable 
0 
 
00-48  Display filter time (Current) 0.001~65.535 sec.  0.100 
 
00-49  Display filter time (Keypad)  0.001~65.535 sec.  0.100 
 
00-50  Software version (Date)  Read only  #####