NO.6 Detailed Function Description
60
Figure 6-15 High/Low-speed Operating Time Curve of Pump
P134
Setting range
Unit
Ex-factory value
Alteration
Low-speed operating time
1-250s
1s
60
○
During the application of constant pressure water supply, when main pump frequency
operates at low speed (set via P061) due to reduction of water consumption and low-speed
operating time (P134) is achieved, corresponding multi-function contact shall be actuated
and auxiliary pumps stop.
P133 and P134 must be used in coordination with p060, P061 and multi-function output
terminal and mainly used for addition and reduction of auxiliary pumps. Refer to Figure 6-15
for details.
P135
Setting range
Unit
Ex-factory value
Alteration
Shutdown pressure level
0-150%
1%
95
○
P136
1-250s
1s
30
○
Shutdown level
continuous time
P137
1-150%
1%
80
○
Wake-up level
P138
0.00-400.0
0.01
Hz
20.00
○
Sleep frequency
P139
1-250s
1s
20
○
Sleep frequency
continuous time
Shutdown pressure level mainly refers to pressure level occurring when main pump enters
the dormancy state; refer to Figure 6-16 for details.
Shutdown level continuous time refers to the duration time on the condition of shutdown
pressure level before going sleep; refer to Figure 6-16 for details.
Wake-up level refers to wake-up pressure level from dormancy state to recovery; refer to