D1000 Installation and Service Manual 35
Home LAB-110073 Rev. 3
AFTER AN ACTUATION
RESETTING THE POWER DISCONNECT
Gas Disconnect
Refer to local codes in bringing the system back to operation.
Observing the recommendation and clearance from the fire officials and make sure all burners are in the OFF
position. Turn off any electric or mechanical devices capable of igniting gas to reduce the risk of explosion due to
leaking gas.
o Done by a licensed and qualified individual.
See Reset the System (page 38).
The gas solenoid valve will energize into its normal operating position (open).
Examine burners for gaseous odor.
o If gas odor exists, turn the main power switch OFF (O).
o This will cause the gas solenoid valve to close and will shut off the gas supply.
Electric Disconnect
Check to ensure the power switch on the top left of the hood is in the ON (I) position
Press the white manual reset button on the top left of the hood
o The status LED will turn from Orange to green
o The disconnect will be energized
If the system does not reset, check for one of the following issues:
Tank hose is not connected properly.
Tank pressure switch wire is disconnected.
Tank does not have adequate pressure.
Power to the hood is OFF.
Maintenance switch is in the ON (I) position.
Check the status LED and audible buzzer for fault codes.