Rev 07/04/2015
2
Parameter
Description
5 PANS
115V
5 PANS
230V
CONTAINED
230V TROLLEY
DCR
differential for restarting blast chiller after high
condenser temperature [°C/°F]
18 18
18 18
RMT
stop time during high condenser
[sec]
180
180 180 180
PMT
max high condenser event before high temp.
Alarm [num]
3
3 3 3
TPB
time threshold for high condenser temp.
[min]
30
30 30 30
DTE
defrost ending temp related to evap.
[°C/°F]
41 41
41 41
DRP dripping time after defrost [sec] 60
60 60 60
DTO defrost timeout [min] 10
10 10 10
ITD
interval between two consecutive defrosts
[hours]
8
8 8 8
DCD max on-time drain heater [min] 8
8 8 8
SDT
ice detecting sensitivity in smart defrost mode
[num]
0
0 0 0
SD1 first daily defrost [hour] 0
0 0 0
SD2 second daily defrost [hour] 0
0 0 0
SD3 third daily defrost [hour] 0
0 0 0
SD4 fourth daily defrost [hour] 0
0 0 0
SPX door frame heater set point [°C/°F] 14 14
14 14
COS average power factor of equipment [num] 5
5 5 5
PR1 declared power connected to relay1 [num] 0
0 0 0
PR2 declared power connected to relay2 [num] 0
0 0 0
PR3 declared power connected to relay3 [num] 0
0 0 0
PR4 declared power connected to relay4 [num] 0
0 0 0
PR5 declared power connected to relay5 [num] 0
0 0 0
PR6 declared power connected to relay6 [num] 0
0 0 0
PR7 declared power connected to relay7 [num] 0
0 0 0
PR8 declared power connected to relay8 [num] 0
0 0 0
STB number of cycles during D test [num] 5
5 5 5
CYC number of on7off cycles during D test [num] 5
5 5 5
WIN max pull down time in winter D test [num] 90
90 90 90
SUM max pull down time in summer D test [num] 120
120 120 120
ETT set point in heating cycle during D test [°C/°F] 59 59
59 59
SPU user set point in storage cycle [°C/°F] 37 37
37 37
OF1 cabinet probe offset [num] -0.7
-0.7 -0.7 0
OF2 evaporator probe offset [°C/°F] 0 0
0 0
OF3 condenser probe offset [°C/°F] 0 0
0 0
OF4 core probe point 1 offset [°C/°F] 0 0
0 0
OF5 core probe point 2 offset [°C/°F] 0 0
0 0
OF6 core probe point 3 offset [°C/°F] 0 0
0 0
OF7 core probe point 4 offset [°C/°F] 0 0
0 0