Technical Data
Operating voltage U
B
24 V DC
Voltage tolerance
U
B
90
-
110%
Residual ripple U
B
(DC)
max 10 %
Power consumption at
U
B
max 10 W
Safety contacts
STOP
all
output modules
13
14
23
24
SPEED 1
all
output modules
33
34
43
44
SPEED 2
at GM and GMG
53
54
63
64
SPEED 2
at GM V1, GMG V1, VM and VMG
57
58
67
68
Typical response time/
fall
-
back time of the contact output
15ms
Contact
material
AgNi10 + 5µm Au
Minimal switch current
10mA
Switching capability
according to DIN EN 60947
-
4
-
1/DIN EN 60947
-
5
-
1
DC1: 24V/ 6A, DC13: 24V/ 4A, 0.1Hz
Switching capability
according to DIN EN 60947
-
4
-
1/ EN 60947
-
5
-
1
AC1:250V/ 6A, AC15: 230V/ 3A, 0.1Hz
Sum current from all contact
12A
Contact life
DC13: 24V/ 1A
1.5x10
5
Contact life
DC13: 24V/ 4A
10
4
Contact life AC15: 230V/
0.5
A
2x10
6
Contact life AC15: 230V/ 1A
3x10
5
Mechanical contact life
> 50x10
6
Maximal
cycles
DC13: 4A
360
cycles
/h
Maximal
cycles
AC15: 1
A
360 cycles /h
Contact fuse
6A slow
Short-circuit strength
200A/
B6
automat
800A/safety fuse 6A gl
Maximum contact voltage
250V AC
Surge voltage
strength
, u
se in pollution degree 2 Environment.
4KV
OS
,
OD, O1, O2
0,1A
Operating time
100 %
Internal unit fuse protection
Minimal 1,25A, Maximal: Conductor protection
Operating temperature
DIN IEC 60068-2-3, -10 + 60°C
Storage temperature
DIN IEC 60068-2-3, -40 + 85°C
Vibration tolerance on all 3 levels
Sinus 10
55Hz, 0.35mm, 10 cycles, 1 Octave / min
Maximal frequency at the RJ45 connector
300KHz
Maximal
F
requency at the RJ45 connector
8
00Hz
modulation, 10KHz carrier
Maximal frequency at IN1 and IN2
1500Hz
Repetition accuracy
±
0,1 %
Temperature dependency of the trigger point
0,02 %/°C
Air gap creep age to
VDE 0110 Teil1
Max. lead cross section
Core with crimp connector
Input
terminals:1 x 1,0 mm
2
,
Output terminal: 1 x 1,5 mm
2
Connection wire
60/75°C copper
Terminal
S
pring load
terminal
s, pluggable
Housing metal material
Hosing synthetically material
Sheet steel, powder
-
coated
PVC, PC, PA / VO (UL94)
Protection Only for
housing and terminals: IP20,
cabinet mounting with minimal protection IP 54
Contact durability
24V DC switching voltage: work days every year: 260, 8h every day
Load:
Switch current:
Switch cycles
DC1
1A
384
192
96
DC13
1A
15
7
3.6
DC1
4A
192
96
48
DC13
4A
1
0.5
0.25
DC1
6A
153
76
38
Years
5
10
20
10
Schaltspiele / Cycles
Schaltstrom (A) / Switching current (A)
DC13
24V
AC15
230V
AC1
230V
DC1
24V
7
10
6
10
5
10
4
0.1 0.5 1.0 2.0 3.0 4.0 5
6
10
AC1: control of non-inductive or low inductive load AC voltage
AC15: control of inductive load AC voltage
DC1: control of non-inductive or low inductive load DC voltage
DC13: control of inductive load DC voltage