EasyManua.ls Logo

Distech Controls ECB-PTU Series - Page 9

Distech Controls ECB-PTU Series
24 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9 / 24
Figure18: 0-10 V controller-powered valve wiring (ECB-PTU-107/207/307)
Figure19: 0-10 V controller-powered valve wiring (ECB-PTU-208/308)
Wiring Analog Outputs (AOx)
Analog outputs can be configured to provide either a discrete signal of 0 or 12 VDC or a linear signal ranging from 0 to 10 VDC. The discrete signal can
be used to generate a pulse wave modulation (PWM) signal or a simple two-state signal.
Analog output connectors accept wires between 0.75 mm² (18 AWG) and 1.5 mm² (16 AWG).
If an analog actuator is being controlled, connect the 0 to 10 VDC output, along with an external 24 VAC power source, to the analog actuator according
to the following figure.
Figure20: Self-powered 0-10 V actuator wiring
The onboard 24 VAC power supply can be used to power 0-10 V actuators according to the following figure (ECB-PTU-208 and ECB-PTU-308 only).
Figure21: Controller-powered 0-10 V actuator wiring