Commissioning ECB-Series Controllers
When using an Allure EC-Smart-Vue Series Communicating Sensor for commissioning ECB Series controllers (the DIP switch located on the faceplate is
set to 0 (all off) and before code is downloaded to the controller from EC-
gfx
Program ), connect an Allure EC-Smart-Vue Series Communicating Sensor
to the controller with its Subnet ID set to 1.
During commissioning, the sensor is used to set the controller’s BACnet
®
MAC Address.
Set the connected controller’s MAC Address as follows:
1. Connect an Allure EC-Smart-Vue Series Communicating Sensor to the controller with a Cat 5e patch cable. Wait for the display to show the room
temperature.
2. Press and hold the Menu button for 5 seconds to enter the password menu. 10000 is shown on the display.
OR
Screen Timeout: 15 seconds
3. Use the down button to set the number to 9995 (this is the default password).
OR
Screen Timeout: 15 seconds
4. Press the
Menu
button to submit the password. Upon submitting the password, the
GEN CFG
menu appears on the display.
OR
Screen Timeout: 30 seconds
5. Press the down button once to enter the
GEN CFG
submenu. The
MAC ADDRESS
menu is shown with the current controller’s BACnet MAC Ad-
dress.
OR
Screen Timeout: 30 seconds
6. Use the up and down buttons to set the controller’s MAC Address. Only addresses from 1 to 127 are recommended to be used.
7. Press the Menu button once to apply the value.
8. Press and hold the Menu button for 5 seconds to exit the configuration menu.
Once the controller’s network is operational, the controller can be programmed with EC-
gfx
Program. For each Allure EC-Smart-Vue Series Communicat-
ing Sensor, set its Subnet ID number to the block number of its associated ComSensor block in EC-
gfx
Program. This is done in the sensor’s
GEN CFG
menu under
SUBNET ID
.