1592017050 XLR470 GB r1.0 24.05.07.doc XLR470 18/18
Label Name Range Default level
DEFROST TIMES (ONLY WITH RTC)
L1d1
1
st
workdays defrost start (Section 1) 0 ÷ 23h 50 min. - nu 6.0 Pr2
L1d2
2
nd
workdays defrost start (Section 1) 0 ÷ 23h 50 min. - nu 13.0 Pr2
L1d3
3
rd
workdays defrost start (Section 1) 0 ÷ 23h 50 min. - nu 21.0 Pr2
L1d4
4
th
workdays defrost start (Section 1) 0 ÷ 23h 50 min. - nu nu Pr2
L1d5
5
th
workdays defrost start (Section 1) 0 ÷ 23h 50 min. - nu nu Pr2
L1d6
6
th
workdays defrost start (Section 1) 0 ÷ 23h 50 min. - nu nu Pr2
S1d1
1
st
holiday defrost start (Section 1) 0 ÷ 23h 50 min. - nu nu Pr2
S1d2
2
nd
holiday defrost start (Section 1) 0 ÷ 23h 50 min. - nu nu Pr2
S1d3
3
rd
holiday defrost start (Section 1) 0 ÷ 23h 50 min. - nu nu Pr2
S1d4
4
th
holiday defrost start (Section 1) 0 ÷ 23h 50 min. - nu nu Pr2
S1d5
5
th
holiday defrost start (Section 1) 0 ÷ 23h 50 min. - nu nu Pr2
S1d6
6
th
holiday defrost start (Section 1) 0 ÷ 23h 50 min. - nu nu Pr2
L2d1
1
st
workdays defrost start (Section 2) 0 ÷ 23h 50 min. - nu 6.0 Pr2
L2d2
2
nd
workdays defrost start (Section 2) 0 ÷ 23h 50 min. - nu 13.0 Pr2
L2d3
3
rd
workdays defrost start (Section 2) 0 ÷ 23h 50 min. - nu 21.0 Pr2
L2d4
4
th
workdays defrost start (Section 2) 0 ÷ 23h 50 min. - nu nu Pr2
L2d5
5
th
workdays defrost start (Section 2) 0 ÷ 23h 50 min. - nu nu Pr2
L2d6
6
th
workdays defrost start (Section 2) 0 ÷ 23h 50 min. - nu nu Pr2
S2d1
1
st
holiday defrost start (Section 2) 0 ÷ 23h 50 min. - nu nu Pr2
S2d2
2
nd
holiday defrost start (Section 2) 0 ÷ 23h 50 min. - nu nu Pr2
S2d3
3
rd
holiday defrost start (Section 2) 0 ÷ 23h 50 min. - nu nu Pr2
S2d4
4
th
holiday defrost start (Section 2) 0 ÷ 23h 50 min. - nu nu Pr2
S2d5
5
th
holiday defrost start (Section 2) 0 ÷ 23h 50 min. - nu nu Pr2
S2d6
6
th
holiday defrost start (Section 2) 0 ÷ 23h 50 min. - nu nu Pr2
UTILITY
Adr1
RS485 serial address, section 1 1÷247
1 Pr2
Adr2
RS485 serial address, section 2 1÷247
1 Pr2
dP1
Thermostat 1 probe value - - -
- - - Pr1
dP2
Evaporator 1 probe value - - -
- - - Pr1
dP3
Thermostat 2 probe value - - -
- - - Pr1
dP4
Evaporator 2 probe value - - -
- - - Pr1
rEL
Release software --- - - - Pr2
Ptb
Parameter table - - - - - - Pr2
Pr2
Access to the protected parameter list - - - Pr1