Fire Alarm Panel FP9000A
DMTech LTD, 16 N.Haytov Street, Pleven Tel.: 0889992660 e-mail:office@dmtech-ltd.com page - 11 - of 20
ISO 9001:2015 Certified Company
2.2.4. Connecting the main supply
Power to the fire alarm panel is provided by connecting the main power supply cable to a 220V terminal, installed
in fire alarm panel’s box, see Fig.5, position 2. The wiring between the 220V terminal and the power supply unit
is done by the producer. The connection between the main power supply cable and the 220V terminal is shown
in Fig.3.
2.2.5. Connecting the storage battery
Storage battery connecting pins are situated at the base of the PCB. The connection to the storage battery is
shown in Fig.7. The fire alarm panel box has a cable, with installed cable ear terminals for serial connection of
storage batteries.
WARNING: Storage battery must be charged at maximum current value I = 2A
and voltage U = 27.2V ±1%.
12V Ah5
12V Ah5
+
+
5
червен
+
battery
мост с кабелни обувки
Fig. 7 Connecting the storage batteries