To each zone can be connected up to 80 units, of which 60 fire detectors and 20 Input-Output devices, thus
providing easy adaptation of the system to any type of configuration. To avoid or reduce significantly possible
problems during system installation it shall be carefully designed before the final installation of the panel and the
fire detectors. The design includes: assigning an address to each device and planning a name for it, maximum
length 20 symbols (spaces included), so it can be easily found in the configured system.
The devices shall be grouped in zones in compliance with current standards applicable to installation of
fire alarm systems and according to building blueprints.
1.2. General characteristics
The front panel consists of alphanumeric LCD display (4 lines x 20 symbols), functional buttons and LED
indicators. Access to panel functions is organized in three separate levels.
The fire alarm panel has a built-in real-time clock and calendar, allowing for day mode and night mode of
operation. Switching between the two modes is done automatically or manually. Events like FIRE, RESET,
FAULT, etc. are being stored in the memory, creating a log file of events. The log file contains time and date,
address and name of device, number and name of zone, etc.