COMBO DRIVE FOR UPC SERIES
47
ALLARME
ALARM CODE
INCONVENIENTE
FAULT
POSSIBILI CAUSE
POSSIBLE CAUSES
RIMEDI
SOLUTIONS
EFFETTO
Power+ n°
Circuito 1/2/3/4
0: Nessun errore
1: Sovracorrente
2: Sovraccarico Motore
3: Sovratensione
4: Sottotensione
5: Sovratemperatura
6: Sottotemperatura
7: Sovracorrente HW
8: Sovrat. Motore
9: Guasto drive
10: Errore CPU
11: Parametri di default
12: Ondulazione DC bus
13: Timeout comunic.
14: Err.Termistore
15: Err.Autotuning
16: Drive disabilitato
17: Manca fase motore
18: Ventola guasta
19: Motore in stallo
20: Guasto modulo PFC
21: Codice err.21
22: Sottotensione PFC
23: Errore lettura STO
24: Errore lettura STO
25: Err.messa terra
26: Errore interno 1
27: Errore interno 2
28: Sovratensione drive
30: Codice all.30
98:Avvio inv Inatteso
99:Stop inv Inatteso
Funzionamento dell’inverter
fuori dai limiti stabiliti.
Aspettare qualche minuto,
Provare a resettare
l’allarme.
Se si ripresenta contattare
l’assistenza.
Stop compressore.
Power+ n°
Circuito 1/2/3/4
0: No fault
1: Overcurrent
2: Motor overload /
3: Overvoltage
4: Undervoltage
5: Drive overtempt.
6: Drive underTemp.
7: Overcurrent HW
8: Motor overtemp.
9: Drive failure
10: Cpu error
11: Param. Default
12: DC bus ripple
13: Data comms fault
14: Drive thermistor
15: Autotune fault
16: Drive disabled
17: Motor phase
18: Fan fault
19: Speed fault
20: PFC failure
21: error code 21
22: PFC undervoltage
23: STO survey fail
24: STO survey fail
25: Ground fault
26: Internal error 1
27: Internal error 2
28: Drive overload
30: error code 30
98:Unexp.Inv. Restart
99:Unexp.Inverter Stop
Operation of the inverter
outside the established limits.
Wait a few minuts, try
resetting the alarm.
If it reappears contact
support.
Stop compressor.