15
o CW Return
o Input B001
o Offsett 0.0 (Default)
o Value Actual Value
Scroll to view additional analog sensors for calibration.
Sub Menu C: Control Loops
This menu allows you to set the superheat setpoint and other PID parameters for the valve and drive.
NOTE: Do not make changes to the PID loops.
o Superheat
o Cool Setpoint: 10 F (Default)
o Heat Setpoint: 10 F (Default)
Next screen
o Setpoint SH: 10K (Default)
o LowSH thresh: 2.0K (Default)
o LOP thresh: -50.0 C (Default)
o MOP thresh: 26.0 C (Default)
Next screen
Modulating Setup (PID)
o Compressor
o Input Actual Value
o Output Actual Value
o Setpoint 8.9 (Default)
o Band: 11.0 (Default)
o Integration Time: 20 (Default)
Sub Menu D: User Save
This is used to save any user specific settings.
o Save? No (Default) Yes
o Restore? No (Default) Yes
o Enable Auto Save: Yes (Default) No
Next screen
This will clear the Alarm History. This is only to be used once the unit has been commissioned.
o Continue? No (Default) Yes
Sub Menu E: Stage Address
This menu is to be used in a multistage configuration to change the additional unit addresses. This is to be done
so that there are no address conflicts when daisy chaining the additional unit mod bus connections. This must
be done prior to connecting all the units together, via Modbus connections.
o pLAN Board Addressing