16
o Current Address: 1(Default)
o Change Address to: 1(Default)
Next Screen
o Unit Settings
o Num of Stages 1 (Default) Max 4
Sub Menu: F Stage Disable
This menu is to be used when in a multistage configuration. This allows a technician to take a stage off-line so
that repairs can be made and the rest of the system be operational in auto mode. The system must be in an off
state to enable stage control. Disabling a stage via breaker will cause system to go into a “Limp Mode”.
o Maintenance
o Stage Control: No (Default) Yes.
If Enabled,
o Stage 1: Enabled (Default) Disabled
o Stage 2: Enabled (Default) Disabled
o Stage 3: Enabled (Default) Disabled
o Stage 4: Enabled (Default) Disabled
Sub Menu F: Manual Management
This menu allows the technician to manually operate the relay outputs as well as enable or disable analog sensors.
o Sub Menu A: Analog Input
o CW Return
o Manual Control B001: Off (Default) On
o Manual Position: Value Desired
o Value: Actual Value
Scroll to adjust additional sensors
o Sub Menu B: Digital Input
o Flow Switch
o Manual DI 3: Off (Default) ON
o Manual Position: Actual (Enter Desired Position)
o DI Input Status: Actual Value
Scroll to adjust additional inputs
o Sub Menu C: Relay Output
o SW Pump
o Manual Relay 1: OFF (Default) No
o Manual Position: OFF (Enter Desired)
o Relay Status: Actual Posi in tion
Scroll to adjust additional Outputs
o Sub Menu D:Analog Outputs
o NOT USED