3.5.3Sensor related commands
RS485 Debug Command
This command is used to configure the RS485 devices; they won’t be used during sampling.
AT Command
AT+CFGDEV=xx xx xx xx xx xx xx xx xx xx xx xx,m m: 0: no CRC, 1: add CRC-16/MODBUS in the
end of this command
Downlink Payload
Format: A8 MM NN XX XX XX XX YY
Where:
MM: 1: add CRC-16/MODBUS ; 0: no CRC
NN: The length of RS485 command
XX XX XX XX: RS485 command total NN bytes
YY: How many bytes will be uplink from the return of this RS485 command,
if YY=0, RS485-LN will execute the downlink command without uplink;
if YY>0, RS485-LN will uplink total YY bytes from the output of this RS485 command; Fport=200
if YY=FF, RS485-LN will uplink RS485 output with the downlink command content; Fport=200.
Example 1 --> Configure without ask for uplink (YY=0)
To connect a Modbus Alarm with below commands.
The command to active alarm is: 0A 05 00 04 00 01 4C B0. Where 0A 05 00 04 00 01 is the Modbus
command to read the register 00 40 where stored the DI status. The 4C B0 is the CRC-16/MODBUS which
calculate manually.
The command to deactivate alarm is: 0A 05 00 04 00 00 8D 70. Where 0A 05 00 04 00 00 is the Modbus
command to read the register 00 40 where stored the DI status. The 8D 70 is the CRC-16/MODBUS which
calculate manually.
So if user want to use downlink command to control to RS485 Alarm, he can use:
A8 01 06 0A 05 00 04 00 01 00: to activate the RS485 Alarm
A8 01 06 0A 05 00 04 00 00 00: to deactivate the RS485 Alarm
A8 is type code and 01 means add CRC-16/MODBUS at the end, the 3
rd
byte is 06, means the next 6 bytes are the
command to be sent to the RS485 network, the final byte 00 means this command don’t need to acquire output.
Example 2 --> Configure with requesting uplink and original downlink command (YY=FF)
User in IoT server send a downlink command: A8 01 06 0A 08 00 04 00 01 YY
RS485-LN got this downlink command and send 0A 08 00 04 00 01to Modbus network. One of the RS485 sensor
in the network send back Modbus reply 0A 08 00 04 00 00. RS485-LN get this reply and combine with the original
downlink command and uplink. The uplink message is: A8 0A 08 00 04 0001 06 0A 08 00 04 00 00
Page 24 / 38 - last modified by Bei Jinggeng on 2022/07/08 16:50

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Dragino RS485-LN and is the answer not in the manual?

Dragino RS485-LN Specifications

General IconGeneral
BrandDragino
ModelRS485-LN
CategoryMedia Converter
LanguageEnglish