07-01674N F410, F411 9 Dri-Eaz Products, Inc.
SYSTEM MESSAGES
The Control Panel will display the following messages based on system performance and environmental conditions. User
action, if any is required, is indicated in the third column.
CONTROL PANEL
MESSAGE
EXPLANATION USER ACTION
Indicates control board firmware version number.
Unit has finished powering up and is operating.
PLEASE WAIT
COMP. DELAY XX
60s delay before compressor turns on. Allows system
pressure to equalize.
INLET XXX°F / XX%
First line: indicates total operating hours.
Second line: Toggles between inlet temperature and
inlet RH every 2 seconds.
INLET XXX°F / XX%
First line: indicates unit is in humidistat mode
Second line: Toggles between inlet temperature and
inlet RH every 2 seconds.
INLET XXX°F/ XX%
Unit shuts off if inlet temp below 45°F/7°C. Turns back on
when inlet reaches 50°F/10°C.
---
PUMP PURGING XX
Pump is purging with countdown in seconds. Press key
again to stop if needed.
HI TEMP CYCLE
REMAINING XX MIN
Unit overload limit reached. Cool-down initiated.
Unit is defrosting, with countdown in seconds.
DEFROST XXX
Unit turned off when coil is cold or already in a defrost
cycle. Proceeds to finish cycle or initiate one to clear
the coils of ice before storage.
Occurs when unit is turned off and coil is not frozen.
Clears the coils of water before storage.
Change filter. Press the > key
to reset
Prompt to clean coils and interior.
Clean coils. Press the > key
to reset