Loading...
9
4 possible baud rates 300, 600, 1200 and 2400
4-wire (QUAD) hook-up to COMBUS
Nominal current draw of 35 mA
Provides Tamper Reporting Codes
Low COMBUS supervision to PC4020 Main Board
PC4700 Fire Module
One module per system
2 wire Class B/Style B smoke detector circuit (20 detectors
maximum)
4-wire Class D/ Style D waterflow circuit (5 sensor
maximum [NFPA 3-8-6-3])
1 fully programmable supervised bell output. (Controlled
via the Main Bell Output)
Dual supervised Telco lines - With the ability to switch to
the second line in the event of a line failure.
Ground fault detection
Nominal current draw of 35mA
4-wire quad connection to Combus
Low Combus supervision to the Main Board
Reporting codes for:
- Bell CCT Trouble
- Waterflow Alarm/Trouble
- 2 Wire smoke Alarm/Trouble
- TLM trouble/restoral for line 1 and line 2
- Ground Fault
LCD4500 Remote Keypad
Up to 16 keypads on system
Alphanumeric liquid crystal display
Built-in piezoelectric buzzer
Full annunciation of zones and system status
4-wire (QUAD) hook-up to COMBUS
Nominal current draw of 25 mA (maximum 55 mA)
Provides Tamper Reporting Codes
Low COMBUS supervision to PC4020 Main Board
Dimensions 5.75" x 4.5" x 1" deep (144 x 114 x 25 mm)
Escort 4580 (Voice Prompting Module)
One module per system
Full voice prompts for all major user accessible sections
4-wire quad connection to Combus
70ma - 140 ma
Automation Control capabilities - up to 32 Automation
Module per system
Low Combus supervision to the main board
PC4820 Access Control Module
Up to 16 access control modules on the system
4-wire (QUAD) hookup to the COMBUS
2 access card readers supported per module (total of up to
32 access card readers)
2 door inputs that may be assigned to partitions per
module (total of up to 32 door inputs)
Nominal current draw of 35mA
Provides tamper supervision and reporting codes
Low COMBUS supervision to the PC4020KT
AUX output provides 125mA supply power at 13.8V
Provides Lock output supervision to the PC4020
Provides Reader power supervision to the PC4020
PC4108 Expansion Module
Up to 128 zones total on system
8 zone expansion module
Normally closed loops, EOL resistor, Double EOL
resistor support
4-wire (QUAD) hook-up to COMBUS
Nominal current draw of 25 mA
Provides Tamper Reporting Codes
Low COMBUS supervision to PC4020 Main Board
PC4116 Expansion Module
Up to 128 zones in total on system
Normally closed loops, EOL resistor, Double EOL
resistor support
16 zone expansion module
4-wire (QUAD) hook-up to COMBUS
Nominal current draw of 30 mA
Provides Tamper Reporting Codes
Low COMBUS supervision to PC4020 Main Board
PC4164 Expansion Module
Up to 64 zones in total on the system
One module per system
64 zone wireless expansion module
Support for Universal transmitters and PIRs
Normally closed and zone module tamper support
4-wire quad hookup to the PC4164
Nominal current draw of 110mA
Provides zone alarm/zone low battery/zone tamper
reporting codes
Low Combus supervision to the PC4010
PC4204 High Current Output Module
4 output high current module
Up to 16 modules on system
Minimum 40 VA 16-18 volt transformer required
Minimum 4 Amp-Hour, 12 volt battery required
Each output programmable for 1 of 35 options
4-wire (QUAD) hook-up to COMBUS
Nominal current draw of 25 mA
Provides Tamper and Trouble Reporting Codes
Low COMBUS supervision to PC4020 Main Board
1.5 Amp output
PC4216 Low Current Output Module
16 output low current module
Up to 9 modules on system
All module programmable for all 16 outputs, 1 of 35
options for each
8 modules programmable as alarm annunciators or
zone followers
4-wire (QUAD) hook-up to COMBUS
Nominal current draw of 35 mA
Provides Tamper Reporting Codes
Low COMBUS supervision to PC4020 Main Board
PC4400 RS-232 Interface Adapter Module
True RS-232 technology
Handshake software switches
Protocol XON/XOFF or DTR
MODULE
SPECIFICATIONS

Table of Contents