34
[016] Fourth System Option Code
Default Option ON Off Section Page #
ON
I________I 1 AC Trouble Displayed AC Trouble Not Displayed 3.4 8
OFF
I________I 2 Trouble Light Flashes if AC Fails Trouble Light Does Not Follow AC Status 3.4 8
OFF
I________I 3 Blank Keypad When Not Used Keypad Active Always 5.23 26
OFF
I________I 4 Code Required to Remove Kypd BlankingNo Code Required 5.23 26
ON
I________I 5 Keypad Backlighting is enabled Keypad Backlighting is disabled 5.24 26
OFF
I________I 6 Power Save Mode enabled Power Save Mode disabled 5.23 26
OFF
I________I 7 Bypass Status Displayed While Armed Bypass Status Not Displayed While Armed 5.18 24
OFF
I________I 8 Keypad Tampers enabled Keypad Tampers disabled 5.26 26
[017] Fifth System Option Code
Default Option ON Off Section Page #
ON
I________I 1 WLS Key Does Not Use Access Codes* WLS Key Uses Access Codes 5.18 24
OFF
I________I 2-7 For Future Use
OFF
I________I 8 Squawk on Away Arming/Disarming OnlyBell Squawk on all Arming/Disarming 5.18 24
*This option must be enabled when using a PC5132 v2.1 or earlier.
[018] Sixth System Option Code
Default Option ON Off Section Page #
OFF I________I 1 For Future Use
OFF
I________I 2 For Future Use
OFF
I________I 3 For Future Use
OFF
I________I 4 Contact ID Partial Close Identifier is 5 Contact ID Partial Close Identifier is 4 5.10 19
OFF
I________I 5 For Future Use
OFF
I________I 6 Audible RF Jam Trouble Beeps Silent RF Jam Trouble Beeps 3.4 9
OFF
I________I 7 For Future Use
OFF
I________I 8 For Future Use
[020] Keypad Zone Assignments
(Section 2.13 “Keypad Zones” on page 6)
NOTE:Only one keypad may be assigned to a zone.
Default
00
I________I_______I Keypad (slot 1) Zone Valid entries are zones 01-08
00
I________I_______I Keypad (slot 2) Zone Valid entries are zones 01-08
00
I________I_______I Keypad (slot 3) Zone Valid entries are zones 01-08
00
I________I_______I Keypad (slot 4) Zone Valid entries are zones 01-08
00
I________I_______I Keypad (slot 5) Zone Valid entries are zones 01-08
00
I________I_______I Keypad (slot 6) Zone Valid entries are zones 01-08
00
I________I_______I Keypad (slot 7) Zone Valid entries are zones 01-08
00
I________I_______I Keypad (slot 8) Zone Valid entries are zones 01-08
[030] Zone Loop Response Options
Default Option ON Off Section Page #
OFF
I________I 1 Zone 1 is Fast Loop Response Zone 1 is Normal Loop Response 5.25 26
OFF
I________I 2 Zone 2 is Fast Loop Response Zone 2 is Normal Loop Response 5.25 26
OFF
I________I 3 Zone 3 is Fast Loop Response Zone 3 is Normal Loop Response 5.25 26
OFF
I________I 4 Zone 4 is Fast Loop Response Zone 4 is Normal Loop Response 5.25 26
OFF
I________I 5 Zone 5 is Fast Loop Response Zone 5 is Normal Loop Response 5.25 26
OFF
I________I 6 Zone 6 is Fast Loop Response Zone 6 is Normal Loop Response 5.25 26
OFF
I________I 7-8 For future use
NOTE: When Zone Doubler (Option 5, Section 013) is enabled, the Loop Response will be normal (OFF).