11
At the selected auto-arm time, the keypad buzzers will sound for a programmed amount of time
(programmable by the installer only) to warn that an auto-arm is in progress. The bell can also be
programmed to squawk once every 10 seconds during this warning period. When the warning
period is complete, the system will arm with no exit delay and in the Away Mode.
Auto-arming can be cancelled or postponed by entering a valid access code only, during the pro-
grammed warning period. Auto-arming will be attempted at the same time the next day. When the
auto-arming
process is cancelled or postponed, the Auto-arm Cancellation Reporting Code will be
transmitted (if programmed).
If arming is inhibited by one of the following, the Auto-arm Cancellation transmission will be com-
municated.
AC / DC Inhibit Arm
Latching System Tampers
Zone Expander Supervisory Fault
[4] System Test
The system’s Bell Output (2s), Keypad Lights and Communicator are tested. This test will also mea-
sure the panel’s standby battery.
[5] Enable DLS / Allow System Service
If enabled, the installer will be able to access Installer Programming by DLS. In case of DLS access this
provides a window where rings will be detected by the panel. The DLS window will remain open for
6hrs, during which time the installer will be able to enter DLS an unlimited number of times. After
the 6-hr window has expired, Installer’s Programming will be unavailable again until the window is
re-opened.
[6] User Call-up
If enabled by the Installer, the panel will make 1 attempt to call the downloading computer. The
downloading computer must be waiting for the panel to call before downloading can be performed.
[7] For Future Use
[8] User Walk Test (For Europe only)
This test allows the user to verify operation of system detectors and notifies the central station that a
Walk Test is in progress.
NOTE: Fire zones, the 'F' key, and 2-wire smoke detectors are excluded from this test.
Violation of these zones will cause the system to exit the walk test then generate and
transmit alarm condition to the central station.
1. Press [][6][8] to enable Walk Test. The system will notify the Central Station that a walk test has
begun.
2. Violate all each detector (zone) in sequence. A squawk will occur at the keypad, all LEDs on the
keypad will flash and the violation will be recorded in the Event Buffer.
3. Restore zones. Press [][6][8] to end the Walk Test. The system will notify the Central Station that
the walk test has been terminated.
NOTE: If a zone is not violated within 15 minutes of activating the Walk Test, the system will
automatically exit the Walk Test and resume normal operation.
Changing Brightness/Contrast
PK5500/RFK5500/RFK5564 keypads
When this option is selected, the keypad will allow you to scroll through 10 different brightness/con-
trast levels.
1. Press [][6][Master code].
2. Use the [<][>] keys to scroll to either Brightness Control or Contrast Control.
3. Press [] to select the setting you want to adjust.
4. a) ‘Brightness Control’: There are multiple backlighting levels. Use the [<][>] keys to scroll to the
desired level.
b) ‘Contrast Control’: There are 10 different display contrast levels. Use the [<][>] keys to scroll to
the desired contrast level.
5. To exit, press [#].

Other manuals for DSC PowerSeries PC1832

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the DSC PowerSeries PC1832 and is the answer not in the manual?

DSC PowerSeries PC1832 Specifications

General IconGeneral
Zones8 on-board, expandable to 32
User Codes48
Keypads SupportedUp to 8
Operating Voltage16.5VAC
Backup Battery12VDC, 7Ah
PGM Outputs2
Wireless Zones32 (requires wireless receiver)
Auxiliary Power Output500 mA @ 12 VDC
Bell Output700mA @ 12VDC (PTC protected)