EasyManua.ls Logo

DSC WS900-19UL

DSC WS900-19UL
69 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix 3: Regulatory Information
Appendix 3: Regulatory Information
This product has been tested and found in compliance with the following standards:
l UL1023 Household Burglar-Alarm System Units
l UL985 Household Fire Warning System Units
l ULC-S545-02 Residential Fire Warning System Control Units
l ORD-C1023-1974 Household Burglar-Alarm System Units
This product has also been tested and found in compliance with the ANSI/SIA CP-01-2014 Control Panel Standard
Features for False Alarm Reduction.
This product is UL/ULC listed under the following categories:
l UTOU/UTOUC Control Units and Accessories, Household System Type
l NBSX/NBSXC Household Burglar Alarm System Units
l AMTB Control Panels, SIA False Alarm Reduction
The product is labeled with the UL and ULC listing marks along with the SIA CP-01 compliance statement (Also Classified
in accordance with SIA-CP-01 Standard) as proof of compliance with the above mentioned standards. For further inform-
ation on this product’s listings please also refer to the official listing guides published at the UL web site (www.ul.com)
under Certifications Section.
UL/ULC Residential Fire and Burglary Installations:
For ULC Installations refer to the Standard for the Installation of Residential Fire Warning Systems, CAN/ULC-S540.
l Use at least one PG9916 or PG9926 Smoke Detector for Fire Installations (refer to Installer portal > Panel Settings>
Zones> Add Device (Enter Device Serial # or Auto Enroll) > Type >Standard Fire)
l The entry delay shall not exceed 60 seconds (refer to Installer portal > Panel Settings>Panel Configuration>Partition
Configuration> Entry Delay 1)
l The exit delay shall not exceed 120 seconds (refer to Installer portal > Panel Settings>Panel Configuration>Partition
Configuration> Exit Delay)
l The minimum Bell Time-out is 4 minutes (refer to Installer portal > Panel Settings>Panel Configuration>System Con-
figuration> Burglary Bell Time-out)
Note: For ULC Residential Fire Installations the minimum Bell Time-out is 5 minutes
l Temporal Three Fire Signal shall be enabled (hardcoded ON)
l Arm/Disarm Bell Squawk shall be enabled when using wireless key PG9929, PG9939 or PG9949 (refer to Installer
portal > Panel Settings>Panel Configuration>System Configuration> > Local arm shall be ON)
l A code shall be required for bypassing (refer to Installer portal >Panel Settings>Panel Configuration>System Con-
figuration> Access Code Is Required for Bypassing)
l Trouble beeps shall be enabled (refer to Installer portal >Panel Settings>Panel Configuration>System Con-
figuration> Trouble Beeps Auto Silence)
Note: This product is programmed to perform 5 attempts for communication of an event to the supervising station. If unsuc-
cessful, a Fail To Communicate (FTC) trouble is generated.
l Test transmission cycle shall be set for monthly transmission (refer to Installer portal > Panel Settings>Panel Con-
figuration>Comms Configuration> Ethernet Test Transmission Cycle & Cellular Test Transmission Cycle)
l For UL installations, 2 repeaters (model PG9920) must be used for proper signal routing.
Note: For ULC Residential installations set for daily test transmission
l Wireless Supervision window shall be enabled (refer to Installer portal > Account Details > Panel Configuration > Eth-
ernet Supervision, Cellular Supervision)
- 57 -

Table of Contents