EasyManua.ls Logo

dynatherm FP Series - Page 24

dynatherm FP Series
27 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page | 24
APPLIANCE
VENTING
ARRANGEMENT
BOILER
MODEL
BURNER
MODEL
FIRING RATE
INPUT VALUE US
GPH OR BTU/HR
NOZZLE
SIZE
AIR
SETTING
TURBULATOR
OR HEAD
SETTING
PUMP OR
MANIFOLD
PRESSURE
FLANGE
INSERTION
DEPTH
Chimney Vented
FP24 Oil
40 F5
w/SBT
0.85 GPH
0.75x80°B
2.8
0.0
145 psig
2.5” to flange
FP24 Oil
40 F5
w/SBT
1.00 GPH
0.85x80°B
3.0
1.0
FP24 Oil
40 F5
w/SBT
1.25 GPH
1.10x80°B
3.25
3.0
Direct Vented
FP24 DV
40 BF5 DV
w/SBT
0.85 GPH
0.75x80°B
3.5
0.0
145 psig
2.5” to flange
FP24 DV
40 BF5 DV
w/SBT
1.00 GPH
0.85x80°B
4.0
1.0
FP24 DV
40 BF5 DV
w/SBT
1.25 GPH
1.10x80°B
5.5
3.0
Chimney Vented
FP24 Gas
40 G200
w/SBT
119,000 BTU
2.0 mm
2.0
2.0
.85 w.c.
Fixed
FP24 Gas
40 G200
w/SBT
140,000 BTU
2.0 mm
2.25
3.0
1.0 w.c.
FP24 Gas
40 G200
w/SBT
175,000 BTU
2.0 mm
3.0
4.0
1.45 w.c.
Chimney Vented
FP36 Oil
40 F5
w/SBT
1.00 GPH
1.00x30°W
3.1
2.0
156 psig
2.5” to flange
FP36 Oil
40 F5
w/SBT
1.10 GPH
1.10x30°W
3.3
3.0
150 psig
FP36 Oil
40 F5
w/SBT
1.25 GPH
1.25x30°W
3.9
4.0
144 psig
Chimney Vented
FP36 Gas
40 G400
w/SBT
175,000 BTU
C1
1.6
0.0
3.90 w.c.
Fixed
FP36 Gas
40 G400
w/SBT
189,000 BTU
C1
1.9
0.0
4.65 w.c.
FP36 Gas
40 G400
w/SBT
210,000 BTU
C14
2.5
0.0
4.35 w.c.
Chimney Vented
FP48 Oil
40 F10
w/LBT
1.65 GPH
1.50x30°B
3.0
2.0
145 psig
2.5” to flange
FP48 Oil
40 F10
w/LBT
2.00 GPH
1.75x30°B
4.0
3.0
160 psig
FP48 Oil
40 F10
w/LBT
2.25 GPH
2.00x30°B
5.0
4.0
155 psig
Chimney Vented
FP48 Gas
40 G400
w/SBT
231,000 BTU
C3
2.6
1
4.25 w.c.
Fixed
FP48 Gas
40 G400
w/SBT
280,000 BTU
C4
3.5
1
4.55 w.c.
FP48 Gas
40 G400
w/SBT
315,000 BTU
C5
4.2
1
4.10 w.c.
NOTES:
A) All oil burner nozzles listed above are Delavan.