CLASS 2000 METER
62-0389-03 22
6.3 KWh Meter Hardware Functions
6.4 Class 1000 and Class 2000 Pulse Output
Removable Two-Screw Terminal Plug
PULSE VALUE GUIDE FOR CLASS 1000 & 2000, KWH & OR KW DEMAND METER
Color Code Key of Sensor Arrow Must Match the Amperage of Meter:
Pulse output signal is a 50/50 duty cycle. There is no voltage present at the pulse
output connection. It is a solid state relay, and there is no polarity associated with the
relay. The interface range is from 4.5 to 28 VDC, with a maximum of 50 mA.
IDR Jack 8-pin RJ-45-used to connect kWh meter to the E-Mon
Energy automatic meter reading system.
Calibration Jack Connector J11 is for factory calibration only, and is not
a user accessible port. Silicon plug is not to be
removed.
Error LED When lit, indicates that the current sensor is backwards
or on the incorrect phase.
Meter Pulse LED Blinks to show the meter load. Blink rate increases with
load.
Power On LED When lit, indicates power to meter is on.
Pulse Output Optically isolated output pulse for connection to BAS or
peripheral equipment.
Purple White Brown Red Yellow Black Blue Two Blue
25 Amp 50 Amp 100 Amp 200 Amp 400 Amp 800 Amp 1600 Amp 3200 Amp
Watt Hours per Pulse
0.48828 0.97656 1.95312 3.90625 7.81250 15.6250 31.2500 62.500