2.0 Meter Technical Specifi cations
Ordering Information: Defi ne input voltage, current sensor rating, application
GN 208 200 R
Green Net Meter
Input Voltage
Current Sensor Rating
Application (R=Outdoor, blank=indoor)
Input Voltage Confi guration: 3-Wire (Delta) or 4-Wire (Wye)
MAINS Voltage Input: Up to 480 VAC RMS Available
Input Power: 6VA Maximum Rating
Current Sensor Rating: Up to 3200 Amp RMS AC Available
Power Factor: .5 leading or lagging
Line Frequency: 50-60 Hz
Metering Accuracy: Certifi ed to ANSI C12.16
Voltage Operating Range: +/-10% of rated load
Temperature Range (Indoor): -20 degrees C to +50 degrees C
Temperature Range (Outdoor): -20 degrees C to +70 degrees C
Relative Humidity Range: 0-95% Non-Condensing
Voltage Overload: +25% Continuously; +100% for 20 Cycles
Current Sensor Overload: 100% for 1 minute without damaging meter
Pollution Degree: Degree 2 In Accordance with IEC 664
Installation (Overvoltage) Category: Category III
Measurement Category: Category III
Indoor Housing Rating: NEMA 12/13
Outdoor Housing Rating: NEMA 4X
Display Readout: kWh Accumulated
Page 4