Busbar Runs
Maintenance
Important!
Hazardous voltages in electrical equipment
can cause severe personel injury or death
unless otherwise specied. Installation,
inspection and preventive maintenance
should only be performed on busbar system
to which power been turned off, disconnected
and electrically isolated so that no accidential
contact can be made with energized parts.
Operation of busbar trunking which has
been water or moisture damaged can cause
property damage, severe personal injury, or
death. Observe the precautions to assure
adequate insulation resistance and that
sources of moisture are eliminated. Latest IEC
61439-6 and locally applicable safety related
work practices should be followed at all times.
1- EAE tap off boxes are not equipped with any
protective device unless they are required by
customer. Any type of devices can be xed in
tap off boxes providing specic informations
about device prior to manufacture in order to
adjust interlock mechanism.
2- Tap off boxes operating mechanisms of all
electrical & mechanical interlocks should be
exersized to determine that they operate freely
to their full on and off positions.
3- The total continuous load current should be
measured by proper instrument that does not
exceed the current rating on the busbar name
plate or the designated design current.
4- After performing all of the above inspections
and necessary repairs, it may be desirable to
perform an infra-red temperature test on all
electrical connections after busbar system
is re-energized and reaches a stabilized
operating temperature.
Tap Off Boxes With Protective Devices
Important!
Hydrocarbon spray propellants and,
hydrocarbon based sprays or compounds will
cause degradation of certain plastics. Contact
EAE before using these products to clean, dary,
or lubricate components during installation or
maintenance.
1- An external inspection of the system should
be carried out once a year.
2- Any dripping or other source of moisture
onto the busbar modules should be eliminated
from installed area.