SDM630MCT M-bus Series User Manual 2025 V1.00
2025 EASTRON ELECTRONIC. When electricity matter www.eastrongroup.com
6
Over-voltage Category
CAT III
Installation category
CAT III
Current Inputs
Require External Current Transformer for Insulation
Insulating encased meter of protective
class
II
Parameters
Resolution
Voltage
0.1V
Current
0.1A
Frequency
0.01Hz
Power factor
0.001
Active Power
0.01kW
Reactive power
0.01kVAr
Apparent power
0.01kVA
Active energy
0.1kWh
Reactive energy
0.1kVArh
M-bus Communication
The meter provides an M-Bus port for remote communication. The protocol fully comply with EN13757-3.
The following communication parameters can be configured via M-bus communication:
Baud rate
600, 1200, 2400(default), 4800, 9600bps
Parity
NONE/ ODD / EVEN(default)
Stop bits
1 or 2
M-Bus network primary address
001 to 250
M-Bus network secondary address
00 00 00 00 to 99 99 99 99
(default: the last 8 digits of SN)