4 Eaton 9395XC UPS 1200kW/1200kVA, 1350kW/1350kVA or 1500kW/1500kVA 164001079—Rev 01
11..11..33 CCuussttoommeerr IInntteerrffaaccee
• Building Alarm Monitoring. Up to five inputs in the UPS are available to connect the facility's alarm
system contacts. Some system configurations may limit the number of inputs available. The UPS uses
these inputs to monitor the building alarms in addition to the UPS status. See Chapter 8 Communication
for additional information.
• Alarm Contact. One alarm contact is provided for connection to equipment at the facility, such as a light,
an audible alarm, or a computer terminal. The equipment connected to this contact alerts you to a UPS
alarm. See Chapter 8 Communication for additional information.
• Minislot
®
Communication Bays. Four communication bays are standard equipment. One to four optional
Minislot
®
connectivity cards can be installed in the UPS module at any time. Minislot cards are quickly
installed at the front of the UPS and are hot-pluggable. See Chapter 8 Communication for additional
information.
11..11..44 AAddvvaanncceedd BBaatttteerryy MMaannaaggeemmeenntt
A three-stage charging system increases battery service life by optimizing recharge time, and protects batteries
from damage due to high current charging and inverter ripple currents. Charging at high currents can overheat
and damage batteries.
11..11..55 PPoowweerr MMaannaaggeemmeenntt SSooffttwwaarree
Eaton’s Intelligent Power
®
Software solution, based on Web 2.0 technology, includes two applications:
Intelligent Power
®
Manager
™
for UPS management and monitoring, and Intelligent Power
®
Protector
™
, which
allows graceful shutdown of operating systems. See Chapter 8 Communication for additional information.
11..22 OOppttiioonnss aanndd AAcccceessssoorriieess
Contact an Eaton sales representative for information about the following options.
11..22..11 IInntteeggrraatteedd BBaatttteerryy CCaabbiinneettss
Battery backup protection can be provided by equipping the UPS system with Eaton 9395XC battery cabinets
containing sealed lead-acid, maintenance-free batteries. The cabinets are designed for standalone installation
and may be installed adjacent to the UPS or in a separate location. The recommended installation location for
adjacent battery cabinets is on the right side of the UPS cabinet to allow for future expansion using an external
module.
Consult the Eaton
®
Power Xpert
®
9395XC Integrated Battery Cabinet (Models 1085 and 1085HR) Installation
Manual (TBD) for specifics on battery cabinet usage with the 9395XC.
11..22..22 SSyynncc CCoonnttrrooll
An optional Eaton 9395XC Sync Control maintains the critical load outputs of two separate single module
9395XC UPS systems in synchronization. This option facilitates the uninterrupted transfer of the load from one
load bus to another by means of transfer switches. The Sync Control is housed in a wall-mounted panel that
can be located between the UPS units for easy wiring.
11..22..33 SSiinnggllee--FFeeeedd KKiitt
An optional kit is available for converting the dual-feed rectifier and bypass inputs to a single-feed configuration.
The kit consists of jumpers and bus bar extensions for each phase, and the hardware required for installation.
11..22..44 DDiissttrriibbuutteedd BByyppaassss SSyysstteemm
The 9395XC is based on UPS redundancy. Each UPS contains a UPM.
A distributed bypass UPS system with two to five UPSs can be installed to provide a capacity and/or redundant
system. This load sharing system provides more capacity than a single UPS, and can provide backup,
depending on the load and configuration. A Powerware Hot Sync Controller Area Network (CAN) Bridge Card
Introduction