72 Eaton 9395XC UPS 1200kW/1200kVA, 1350kW/1350kVA or 1500kW/1500kVA 164001079—Rev 01
15. Close the door and secure the latch.
Figure 40 shows the wiring connections if the normally-closed REPO contacts are used and Figure 41 shows
alternative methods of connecting a REPO switch if using another manufacturer's switch.
Figure 40. Normally Closed REPO Switch Wiring
3 (NO)
REPO
Switch
(NC)
Twisted
Wires
2 (Return)
NOTE REPO switch rating is 24 Vdc, 1A minimum.
NOTE
The REPO switch must be a latching-type switch not tied to any other circuits.
NOTE REPO normally-open and normally-closed return terminals are separated on the terminal board but are
electrically in common.
1
2
UPS J89
4 (NC)
2 (Return)
UPS System Installation