EasyManua.ls Logo

Eaton 9395XC - Chapter 8 Communication; Minislot Cards

Eaton 9395XC
160 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Eaton 9395XC UPS 1200kW/1200kVA, 1350kW/1350kVA or 1500kW/1500kVA 164001079—Rev 01 129
CChhaapptteerr 88 CCoommmmuunniiccaattiioonn
This chapter describes the communication features of the Eaton Power Xpert 9395XC UPS system and
provides information about connecting hardware. For terminal wiring information, see paragraph
3.2.5 UPS System Interface Wiring Preparation and paragraph 4.7 Installing Interface Connections. For location
of the customer interface panels and terminals, see Figure 27 and Figure 32 through Figure 35.
88..11 MMiinniisslloott CCaarrddss
The Eaton 9395XC UPS has four standard, factory-installed Minislot communication bays. The UPS is
compatible with the following Minislot cards (see Figure 90):
The Power Xpert Gateway Minislot (PXGMS) card provides Web-enabled, real-time monitoring of Eaton
9395XC uninterruptible power systems (UPSs) through standard Web pages, Power Xpert software,
Intelligent Power Manager (IPM), Intelligent Power Protector (IPP), or third-party software. As an integral
part of the Eaton Power Xpert Architecture
®
, the PXGMS card provides a central point to connect UPSs to
the Ethernet network.
Network managers can view critical downstream device information, such as status, power, energy, and
power quality data with an easy-to-use interface.
Industrial Relay Card-Minislot (IRC-MS) can be used to indicate the operating status of the UPS system
using the customer's monitoring equipment. The Industrial Relay Card uses five isolated normally-open or
normally-closed dry relay contacts to indicate the UPS status. Normal, Bypass, Battery, and Alarm modes
can be monitored. See Table 28 for default triggers. The contact ratings and wire range are listed in the
IRC-MS installation guide. One input can be activated by a switch or dry contact. The voltage source is
provided by the card, no external voltage source is needed.
For installation and setup of a Minislot card, contact an Eaton service representative (see paragraph
1.8 Getting Help). Refer to the manual supplied with the Minislot card and associated wiring isolation
bracket for installation instructions.
External wiring from the IRC-MS card should be routed through the upper Interface Entry Conduit Landings
panels (see Figure 28).
Figure 90. Optional Minislot Cards
Ident
Power
Act
100
PXGMS UPS
Restart
TX
RX
Setup
CMN
Status
DHCP
EMP
Ethernet 10/100
+
-
Power Xpert Gateway
(PXGMS) UPS Card
Industrial Relay
(IRC-MS) Card
Table 28. IRC-MS Default Triggers
Relay Trigger
K1
UPS supporting the load
K2
UPS on Battery

Table of Contents